DLO Cable Construction

Voltage:  2000V

Conductor: Fully annealed flexible strand Class I tinned copper

Insulation: Ethylene-Propylene Rubber (EPR)

Sheath: Black heavy duty thermoset CPE (Ozone, sunlight, oil, grease, weather chemical, and abrasion resistant)

Size: All sizes except for 14AWG have tape separator between conductor and insulation

DLO Cable Application:

Diesel Locomotive Cable or DLO Cable is used for wiring of Diesel-electric locomotives, Telecom power supply, Shipyards, Motor Leads, Mining and earth-moving equipment, Oil and gas rigs and in applications where flexibility and durability is required. The cable is suited for use in wet and dry areas, conduits, ducts, troughs, trays and where superior electrical properties are desirable. For applications up to 2000 volts and for temperatures of -40°C to +90°C.

Other Main Application for DLO Cable Are:

  • Railroad and mass transit car wiring
  • General building wire RHH/RHW-2 as per UL 44
  • Deep well submersible pump cable
  • Petrochemical drilling rigs – Offshore and Onshore – MSHA
  • Mining operations
  • Wind turbines
  • Battery power cable
  • Control panel power distribution
  • Earth moving equipment
  • Heavy-duty flexible power cables
  • Portable or fixed installations
  • Leads for motors, generators, batteries, and jumper cables
  • Solar farms

2000V DLO Cable Parameter Data

Part  No. Conductor  Size Nominal thickness (mm) Approxi. OD Approxi. Weight Amps at 90oC (A)
Awg/kcmil Stranding Insulation Outer jacket (mm) (kg/km)
TEBAOFLEX-DLO14 14 19/27 1.14 0.38 4.88 45 35
TEBAOFLEX-DLO12 12 19/25 1.14 0.38 5.46 58 40
TEBAOFLEX-DLO10 10 27/24 1.14 0.76 7.04 83 55
TEBAOFLEX-DLO8 8 41/24 1.4 0.76 7.67 130 80
TEBAOFLEX-DLO6 6 65/24 1.52 0.76 9.4 195 105
TEBAOFLEX-DLO4 4 105/24 1.52 0.76 10.77 301 140
TEBAOFLEX-DLO2 2 168/24 1.52 1.14 13.41 424 190
TEBAOFLEX-DLO1 1 225/24 2.03 1.14 15.57 621 220
TEBAOFLEX-DLO1/0 1/0 273/24 2.03 1.14 17.04 735 260
TEBAOFLEX-DLO2/0 2/0 329/24 2.03 1.14 18.06 874 300
TEBAOFLEX-DLO3/0 3/0 450/24 2.03 1.14 19.99 1068 350
TEBAOFLEX-DLO4/0 4/0 551/24 2.03 1.65 22.45 1257 405
TEBAOFLEX-DLO262 262.6 644/24 2.29 1.65 24.13 1562 471
TEBAOFLEX-DLO313 313.1 772/24 2.29 1.65 25.78 1778 511
TEBAOFLEX-DLO373 373.1 925/24 2.29 1.65 27.58 2059 591
TEBAOFLEX-DLO444 444.4 1091/24 2.29 1.65 29.69 2431 652
TEBAOFLEX-DLO535 535.3 1325/24 2.29 1.65 30.99 2864 728
TEBAOFLEX-DLO646 646.4 1584/24 2.29 1.65 33.3 3433 815
TEBAOFLEX-DLO777 777.7 1925/24 2.29 1.65 35.48 4059 904
TEBAOFLEX-DLO929 929.2 2281/24 2.29 1.65 38.38 5312 1005
TEBAOFLEX-DLO1111 1111 2727/24 3.56 2.41 45.69 6297 1119

Standards:

  • Type RHH/RHW-2 per UL 44
  • Limited Smoke ST1 in accordance with UL1685 vertical flame test
  • Rated RW90-TC for TC use sizes 1/0 & larger
  • IEEE 1202
  • VW-1
  • ICEA S-95-658
  • NEMA WC-70
  • CSA Listed RW90, RW90-TC 1Kv
  • CSA C22.2 No. 38 and No. 230
  • For 1/0 and larger: ST-1, FT-4, IEEE1202, for CT use